SYSTEM OVERVIEW |
|
System overview:
|
"Line-interactive tower
UPS system protects PCs,
network workstations and
other sensitive
electronics from
blackouts, brownouts,
overvoltages and line
noise. Maintains AC
output during blackouts
and continuously
corrects brownouts and
overvoltages from
75-147V back to normal
120V levels. Includes
HID-compliant USB
monitoring port with
cabling, tel/DSL surge
suppression and LED
indicators. PowerAlert
Software available free
via download. "
|
|
Voltage
compatibility:
|
120VAC
|
|
Frequency
compatibility:
|
60Hz
|
|
OUTPUT |
|
Output volt amp
capacity (VA):
|
300
|
|
Output watt
capacity (watts):
|
180
|
|
Output nominal
voltage:
|
120VAC
|
|
Output voltage
regulation:
|
LINE MODE: Sine wave
line voltage 120V
(-18%/+8%), BATTERY
MODE: PWM sine wave
output 115V +/-5%
|
|
Output frequency
regulation:
|
LINE MODE: Passes line
frequency of 60Hz +/-10%
BATTERY MODE: Inverter
output regulated to 60Hz
+/-0.5Hz
|
|
Outlet quantity
/ type:
|
3 NEMA 5-15R
|
|
INPUT |
|
Maximum input
amps:
|
2.1A
|
|
Input connection
type:
|
NEMA 5-15P right angle
|
|
Input cord
length:
|
6 ft., 16 gauge
|
|
Recommended
electrical service:
|
15A 120V
|
|
BATTERY |
|
Full load
runtime:
|
10.5 min. (300VA)
|
|
Half load
runtime:
|
27 min. (150VA)
|
|
DC system
voltage:
|
12V DC
|
|
Typical battery
lifespan:
|
3-6 years, depending on
usage
|
|
Battery recharge
rate:
|
2-4 hours to 90%
|
|
Replacement
Battery Cartridge:
|
RBC51
|
|
VOLTAGE REGULATION |
|
Voltage
regulation description:
|
Automatic voltage
regulation (AVR)
circuits maintain clean,
regulated computer-grade
120V nominal output,
without using battery
power, during brownouts
to 75V and overvoltages
to 147V
|
|
Overvoltage
correction:
|
Input voltages between
128-147VAC are reduced
by 12%
|
|
Direct pass
through:
|
Input voltages between
108-127VAC are passed on
to connected equipment
unchanged
|
|
Brownout
correction:
|
Input voltages between
93-107VAC are boosted by
14%
|
|
Severe brownout
correction:
|
Input voltages between
75-92VAC are boosted by
30%
|
|
LEDS ALARMS &
SWITCHES |
|
Front panel
LEDs:
|
4 front panel LEDs
indicate line power
status, battery power
status, battery
low/replace status and
voltage regulation
operation
|
|
Alarms:
|
Audible alarm with
15-sec. delay sounds to
indicate loss of utility
power. Alarm can be
silenced by pressing
front panel alarm cancel
button. Once silenced,
alarm will re-sound when
approximately 2 min.
runtime remain.
|
|
Switches:
|
Includes 2 front panel
switches - one main
on/off power switch and
one dual function alarm
cancel/self test button
|
|
SURGE / NOISE
SUPPRESSION |
|
AC surge
suppression:
|
480 joules
|
|
AC suppression
response time:
|
Instantaneous
|
|
Dataline
suppression:
|
Tel/DSL
|
|
EMI / RFI AC
noise suppression:
|
Yes
|
|
PHYSICAL |
|
Shipping weight
(lbs):
|
15
|
|
Shipping weight
(kg):
|
6.8
|
|
Unit weight
(lbs):
|
13.5
|
|
Unit weight
(kg):
|
6.1
|
|
Unit Dimensions
(HWD/in):
|
8.5 x 5 x 6.5
|
|
Unit Dimensions
(HWD/cm):
|
21.6 x 12.7 x 16.5
|
|
Shipping
Dimensions (HWD/in):
|
12.25 x 10 x 8.5
|
|
Shipping
Dimensions (HWD/cm):
|
31.1 x 25.4 x 21.6
|
|
Material of
construction:
|
PVC
|
|
Form factors
supported:
|
Tower
|
|
Cooling method:
|
Convection
|
|
Battery Access:
|
Battery access door
allows user replacement
of UPS batteries
|
|
ENVIRONMENTAL |
|
Operating
Temperature:
|
+32 to +104 degrees
Fahrenheit / 0 to +40
degrees Celsius
|
|
Storage
Temperature:
|
+5 to +122 degrees
Fahrenheit / -15 to +50
degrees Celsius
|
|
Relative
Humidity:
|
0 to 95%, non-condensing
|
|
COMMUNICATIONS |
|
Network
monitoring port:
|
USB (HID)
|
|
Software and
cabling included:
|
USB cabling included;
PowerAlert Software
available for free
download at
www.tripplite.com
|
|
WatchDog
compatibility:
|
Compatible with Tripp
Lite's Watchdog system
service to restore
operation to locked
equipment through soft
reboot of application/OS
or hard power off/on
reboot of connected
equipment—ideal for
unattended kiosk
applications
|
|
LINE / BATTERY
TRANSFER |
|
Transfer time
from line power to
battery mode:
|
2-4 milliseconds
|
|
Low voltage
transfer to battery
power:
|
Switches to battery
power as line voltage
decreases to 75V or
less. Resets back to
line power mode as line
voltage increases to 79V
or higher.
|
|
High voltage
transfer to battery
power:
|
Switches to battery
power as line voltage
increases to 147V or
higher. Resets back to
line power mode as line
voltage decreases to
143V or less.
|
|
CERTIFICATIONS |
|
Certifications:
|
Tested to UL1778 (USA),
CSA C22.2 No. 107.3
(Canada), Class B
(emissions), NOM
(Mexico), FCC Part 68 /
Industry Canada
(telecommunications),
RoHS Compliant
|
|
WARRANTY |
|
Product
warranty:
|
2 years
|
|
Connected
equipment insurance (USA
and Canada Only):
|
$200,000 connected
equipment insurance (USA
& Canada only)
|
|
Optional
coverage:
|
3-5 year warranties,
plus next-day and
on-site warranty
coverage available.
Contact Tripp Lite for
additional information.
|
|
SPECIAL FEATURES |
|
Cold Start:
|
Inverter can be cold
started to enable
temporary AC output
during a power failure
|
|
Appearance:
|
Tower format; attractive