Power Factor Inc. is an Eaton Powerware authorized reseller. For information, quote, or to order the Powerware 9315 call us at 800-706-7009.Click here for replacement batteries at our new online store batteriesasap.com Quick turnaround on quotes, Competitive pricing, Fast delivery and Great Customer service!
Powerware 9315 UPS 200 to 500 kVA
Powerware 9315 UPS 200 to 300 kVA Technical Specs
* Specifications subject to change without notice. Model Selection Guide
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
50 Hz Applications |
|||||||
| Model Number | 9315-200 | 9315-250 | |||||
| kVA | 200 | 200 | 200 | 200 | 250 | 250 | |
| kW | 160 | 180 | 160 | 180 | 200 | 225 | |
|
Battery Type |
Number Parallel Strings |
||||||
| J27 - UPS12-270 | 2 | 9 | 7 | 9 | 7 | 5 | - |
| C28 - HRL12280 | 2 | 9 | 7 | 9 | 7 | 5 | - |
| J31 - UPS12-310 | 2 | 11 | 9 | 11 | 9 | 7 | 6 |
| C33 - HRL12330 | 2 | 12 | 10 | 12 | 9 | 8 | 6 |
| J37 - UPS12-370 | 2 | 15 | 11 | 15 | 11 | 11 | 8 |
| C39 - HRL12390 | 2 | 16 | 13 | 16 | 13 | 11 | 9 |
| J47 - UPS12-475 | 2 | 19 | 15 | 19 | 15 | 13 | 9 |
| C50 - HRL12500 | 2 | 20 | 17 | 20 | 17 | 14 | 11 |
| J27 - UPS12-270 | 3 | 17 | 13 | 17 | 13 | 12 | 9 |
| C28 - HRL12280 | 3 | 18 | 14 | 18 | 13 | 13 | 10 |
| J31 - UPS12-310 | 3 | 21 | 18 | 21 | 18 | 15 | 12 |
| C33 - HRL12330 | 3 | 22 | 19 | 22 | 19 | 16 | 13 |
| J37 - UPS12-370 | 3 | 27 | 22 | 27 | 22 | 19 | 15 |
| C39 - HRL12390 | 3 | 27 | 23 | 27 | 23 | 20 | 17 |
| J47 - UPS12-475 | 3 | 37 | 29 | 37 | 29 | 26 | 21 |
| C50 - HRL12500 | 3 | 37 | 30 | 37 | 30 | 27 | 22 |
| J27 - UPS12-270 | 4 | 27 | 21 | 27 | 21 | 19 | 15 |
| C28 - HRL12280 | 4 | 27 | 22 | 27 | 21 | 20 | 16 |
| J31 - UPS12-310 | 4 | 32 | 27 | 32 | 27 | 24 | 19 |
| C33 - HRL12330 | 4 | 33 | 28 | 33 | 28 | 25 | 20 |
| J37 - UPS12-370 | 4 | 39 | 32 | 39 | 32 | 30 | 24 |
| C39 - HRL12390 | 4 | 39 | 33 | 39 | 33 | 30 | 25 |
| J47 - UPS12-475 | 4 | 54 | 46 | 54 | 46 | 41 | 32 |
| C50 - HRL12500 | 4 | 54 | 46 | 54 | 46 | 41 | 33 |
| Nominal DC Link Voltage | 420 | 420 | 420 | 420 | 420 | 420 | |
60 Hz Applications |
|||||||
| Model Number | 9315-225 | 9315-300 | |||||
| kVA | 225 | 225 | 225 | 225 | 300 | 300 | |
| kW | 180 | 202 | 180 | 202 | 240 | 270 | |
|
Battery Type |
Number Parallel Strings |
||||||
| J27 - UPS12-270 | 2 | 9 | 7 | 9 | 7 | - | - |
| C28 - HRL12280 | 2 | 9 | 7 | 9 | 7 | - | - |
| J31 - UPS12-310 | 2 | 12 | 9 | 12 | 9 | 7 | 5 |
| C33 - HRL12330 | 2 | 13 | 10 | 13 | 10 | 7 | 5 |
| J37 - UPS12-370 | 2 | 15 | 12 | 15 | 12 | 9 | 7 |
| C39 - HRL12390 | 2 | 17 | 15 | 17 | 15 | 10 | 7 |
| J47 - UPS12-475 | 2 | 20 | 16 | 20 | 16 | 11 | 8 |
| C50 - HRL12500 | 2 | 22 | 18 | 22 | 18 | 13 | 10 |
| J27 - UPS12-270 | 3 | 17 | 14 | 17 | 14 | 11 | 9 |
| C28 - HRL12280 | 3 | 19 | 16 | 19 | 16 | 12 | 9 |
| J31 - UPS12-310 | 3 | 22 | 18 | 22 | 18 | 14 | 10 |
| C33 - HRL12330 | 3 | 24 | 20 | 24 | 20 | 15 | 13 |
| J37 - UPS12-370 | 3 | 28 | 22 | 28 | 22 | 18 | 14 |
| C39 - HRL12390 | 3 | 29 | 24 | 29 | 24 | 19 | 16 |
| J47 - UPS12-475 | 3 | 38 | 31 | 38 | 31 | 25 | 19 |
| C50 - HRL12500 | 3 | 38 | 32 | 38 | 32 | 26 | 21 |
| J27 - UPS12-270 | 4 | 28 | 22 | 28 | 22 | 17 | 14 |
| C28 - HRL12280 | 4 | 28 | 23 | 28 | 23 | 18 | 15 |
| J31 - UPS12-310 | 4 | 32 | 27 | 32 | 27 | 22 | 18 |
| C33 - HRL12330 | 4 | 33 | 28 | 33 | 28 | 23 | 19 |
| J37 - UPS12-370 | 4 | 40 | 33 | 40 | 33 | 28 | 22 |
| C39 - HRL12390 | 4 | 40 | 34 | 40 | 34 | 28 | 23 |
| J47 - UPS12-475 | 4 | 55 | 48 | 55 | 48 | 38 | 31 |
| C50 - HRL12500 | 4 | 54 | 47 | 54 | 47 | 35 | 29 |
| Nominal DC Link Voltage | 480 | 480 | 480 | 480 | 480 | 480 | |
|
Input |
|
| Voltage Range | See table below |
| Frequency Range | (60 Hz) 57-64 Hz |
| Surge Protection |
Meets ANSI C62.41, Category A & B EN 50091-2 and EN50082-2 |
| Power Factor | 0.95 Typical at full load with input filter |
Output |
|
| Voltage Regulation | Better than +/- 1% |
| Voltage THD |
Less than 5% (100% nonlinear load); Less than 3% (100% linear load) |
| Transient Response | Less than 5% for 100% load, step full recovery within 1 cycle |
| Frequency Regulation | (Free Run) +/- 0.005 Hz |
| Frequency Sync Range | +/- 0.5 Hz |
| Frequency Slew Rate | 1 Hz/sec. |
| Load Crest Ratio | 3:1 |
| Power Factor | 0.9 (Optional) |
Battery |
|
| Battery Type | Sealed, valve regulated lead acid |
| Recharge time | 10-12x discharge to 95% capacity |
| Safety |
UL 1778 Listed CUL CAN/CSA C22.2NO.107.1-M91 Listed All Cabinets provide seismic mounting features selectable DC ground fault detection capability |
Environmental and safety |
|
| Audible Noise | <72 dBA at 1 meter |
| Ambient Operating Temperature | 0°C to 40°C |
| Ambient Storage Temperature | -20°C to +70°C |
| Altitude | 5000 ft. (1500 m) without derating |
| Relative Humidity | 5-95% non-condensing |
| EMI Suppression |
Meet FCC Class A, Subpart J of Part 15 and EN 50091-2 (CIPR22,ClassA) |
| Electrostatic Discharge | Withstands 25kV without damage or disturbance to load |
* Specifications subject to change without notice.
| 9315-400 | 9315-400/300 | 9315-500 | 9315-500/400 | ||||
| 400 kVA/320 kW | 300 kVA/240 kW | 500 kVA/400 kW | 400 kVA/320 kW | ||||
Input Range |
|||||||
| Input Voltage | volts | 400 | 400 | 480 | 480 | 480 | 208 |
Output Voltage |
|||||||
| Output Voltage | volts | 400 | 400 | 480 | 480 | 208 | 208 |
Input Voltage Range |
|||||||
| Minimum | volts | 340 | 340 | 408 | 408 | 408 | 177 |
| Maximum | volts | 440 | 440 | 528 | 528 | 528 | 229 |
| Input /Output Frequency | Hz | 50/60 | 50/60 | 60 | 60 | 60 | 60 |
AC Input (with input filter) |
|||||||
| Nominal Amps | amps | 508 | 381 | 556 | 445 | 445 | 1025 |
| Maximum Amps | amps | 635 | 476 | 640 | 560 | 560 | 1280 |
AC Input (without input filter) |
|||||||
| Nominal Amps | amps | 598 | 448 | 654 | 523 | 523 | N/A |
| Maximum Amps | amps | 747 | 560 | 800 | 640 | 640 | N/A |
Bypass Input |
|||||||
| Nominal Amps | amps | 577 | 433 | 600 | 480 | 480 | 1280 |
AC Output |
|||||||
| Nominal Amps | amps | 577 | 433 | 600 | 480 | 1110 | 1110 |
| 10 Minutes Max. | amps | 721 | 541 | 750 | 600 | 1388 | 1388 |
DC Link |
|||||||
| Nominal DC Voltage | volts | 420 | 420 | 480 | 480 | 480 | 480 |
| Float Voltage | volts | 473 | 473 | 540 | 540 | 540 | 540 |
| End of Discharge | volts | 351 | 351 | 401 | 401 | 401 | 401 |
| Maximum Amps | amps | 914 | 686 | 1000 | 800 | 800 | 800 |
Physical Attributes (with-out battery) |
|||||||
| Installed Weight | lbs | 6100 | 6100 | 6100 | 6100 | 10,100 | 14,100 |
| Installed Width | inches | 74 | 74 | 74 | 74 | 123 | 172 |
System Efficiencies |
|||||||
| 100% Load | % | 94 | 94 | 94 | 92 | 91 | 90 |
| 75% Load | % | 94 | 94 | 94 | 92 | 91 | 90 |
| 50% Load | % | 94 | 93 | 94 | 91 | 90 | 89 |
Full Load Heat Dissipation |
|||||||
| BTU/Hr. (x1000) | 69.8 | 52.3 | 87.2 | 107.3 | 107.3 | 119.0 | |
| KCal/Hr. (x1000) | 17.6 | 13.2 | 22 | 24.1 | 27.1 | 30.0 | |
Inverter Efficiency (full load) |
|||||||
| - | % | 95 | 95 | 95 | 92.5 | 92.5 | 92.5 |
50 Hz Applications |
|||||
| Model Number | 9315-400 | ||||
| kVA | 300 | 300 | 400 | 400 | |
| kW | 240 | 270 | 320 | 360 | |
|
Battery Type |
Number Parallel Strings |
||||
| J37 - UPS12-370 | 2 | 7 | 5 | - | - |
| C39 - HRL12390 | 2 | 7 | 5 | - | - |
| J47 - UPS12-475 | 2 | 8 | 6 | - | - |
| C50 - HRL12500 | 2 | 9 | 7 | - | - |
| J27 - UPS12-270 | 3 | 9 | 7 | - | - |
| C28 - HRL12280 | 3 | 9 | 7 | - | - |
| J31 - UPS12-310 | 3 | 11 | 9 | 6 | - |
| C33 - HRL12330 | 3 | 12 | 9 | 6 | - |
| J37 - UPS12-370 | 3 | 15 | 11 | 9 | 7 |
| C39 - HRL12390 | 3 | 16 | 12 | 10 | 7 |
| J47 - UPS12-475 | 3 | 19 | 15 | 11 | 8 |
| C50 - HRL12500 | 3 | 20 | 16 | 12 | 10 |
| J27 - UPS12-270 | 4 | 14 | 11 | 9 | 7 |
| C28 - HRL12280 | 4 | 14 | 12 | 10 | 7 |
| J31 - UPS12-310 | 4 | 18 | 14 | 11 | 9 |
| C33 - HRL12330 | 4 | 19 | 15 | 12 | 10 |
| J37 - UPS12-370 | 4 | 23 | 19 | 15 | 11 |
| C39 - HRL12390 | 4 | 24 | 20 | 15 | 12 |
| J47 - UPS12-475 | 4 | 31 | 26 | 19 | 15 |
| C50 - HRL12500 | 4 | 31 | 27 | 20 | 16 |
| Nominal DC Link Voltage | 420 | 420 | 420 | 420 | |
60 Hz Applications |
|||||
| Model Number | 9315-500 | ||||
| kVA | 400 | 400 | 500 | 500 | |
| kW | 320 | 360 | 400 | 450 | |
|
Battery Type |
Number Parallel Strings |
||||
| J47 - UPS12-475 | 2 | 5 | - | - | - |
| C50 - HRL12500 | 2 | 6 | - | - | - |
| J27 - UPS12-270 | 3 | 6 | - | - | - |
| C28 - HRL12280 | 3 | 6 | - | - | - |
| J31 - UPS12-310 | 3 | 8 | 6 | 5 | - |
| C33 - HRL12330 | 3 | 9 | 6 | 5 | - |
| J37 - UPS12-370 | 3 | 12 | 9 | 7 | 6 |
| C39 - HRL12390 | 3 | 13 | 10 | 7 | 6 |
| J47 - UPS12-475 | 3 | 15 | 10 | 9 | 7 |
| C50 - HRL12500 | 3 | 17 | 13 | 10 | 7 |
| J27 - UPS12-270 | 4 | 11 | 9 | 7 | 5 |
| C28 - HRL12280 | 4 | 12 | 9 | 7 | 5 |
| J31 - UPS12-310 | 4 | 14 | 10 | 9 | 7 |
| C33 - HRL12330 | 4 | 15 | 12 | 10 | 7 |
| J37 - UPS12-370 | 4 | 18 | 14 | 13 | 10 |
| C39 - HRL12390 | 4 | 19 | 16 | 14 | 11 |
| J47 - UPS12-475 | 4 | 25 | 19 | 17 | 13 |
| C50 - HRL12500 | 4 | 23 | 19 | 18 | 14 |
| Nominal DC Link Voltage | 480 | 480 | 480 | 480 | |
Buy batteries on-line and get it fast!
|
Power Factor Inc. / Batteries ASAP! 2526 Manana Suite 102 Dallas, Texas 75220 800-706-7009 Established 1996 While every precaution has been
taken to ensure accuracy and completeness in this literature, Power Factor Inc.
assumes no responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions. Specifications
subject to change without notice. |