Find the battery you want at the right
price @ batteries asap!
Home CSB Battery Cautions GP Series Features GP Series Technical GP645 GP672 GP6120 GP1222 GP1245 GP1272 GP12120 GP12170 GP12220 GP12260 GP12340 GP12400 GP12650 GP121000 EVX Series Features EVX Series Technical EVX1272 EVX12120 EVX12170 EVX12200 EVX12260 EVX12300 EVX12340 EVX12400 EVX12520 EVX12650 EVX12750 EVX121000 HC Series Features HC Series Technical HC1217W HC1221W HC1225W HC1228W HR Series Features HR Series Technical HR1221W HR1224WF2F1 HR1234WF2 HR1251WF2 HR1290W HR12120WFR
Home
| |
HR1234W is manufactured by CSB (China Storage
Battery). The CSB HR1234W is a 12 Volt 34 Watt per cell / 9 Amp Hour sealed lead acid rechargeable
battery.
HR1234W
|
|
12 V |
34.0w/cell |
|
HR 1234WF2 is
specially
designed for
high efficient
discharge
application. Its
characteristics
are small
volume, light
weight and high
discharge
efficiency. It
can be used for
more than 260
cycles at 100%
discharge in
cycle service,
up to 5 yeas in
standby service.
|
|
|
|
|
Specification |
|
|
Capacity |
34W @ 15
minute-rate to 1.67V per cell @ 25°C
(77°F)
|
|
Weight |
Approx.
2.50kg. (5.51lbs.) |
|
Maximum Discharge current |
130A (5sec.) |
|
Internal Resistance Approx. |
Approx. 19mΩ |
|
Operating Temperature Range |
Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F) |
|
Nominal Operating Temperature Range
|
25°C ± 3°C
(77°F ± 5°F) |
|
Float charging voltage |
13.5 to 13.8
VDC/unit Average at 25°C (77°F) |
|
Recommended Maximum Charging current
limit |
3.4A |
|
Equalization and Cycle Service |
14.4 to 15.0
VDC/unit Average at 25°C (77°F) |
|
Self Discharge |
CSB
Batteries can be stored for more than 6
months at 25°C (77°F) Please charge
batteries before using. For higher
temperatures the time interval will be
shorter. |
|
Terminal |
F1/F2-Faston
Tab187/250 |
|
Container Material |
ABS(UL94-HB/File E50263)*Flammability
resistance of(UL94-V0/File E88367) can
be available upon request. |
Dimensions |
|
|
Constant Current Discharge
Characteristics Unit:Amperes (25℃,77℉)
|
|
F.V/Time |
2MIN |
4MIN |
6MIN |
8MIN |
10MIN |
15MIN |
20MIN |
30MIN |
60MIN |
90MIN |
|
1.60V |
73.84 |
49.16 |
36.83 |
29.74 |
25.39 |
18.49 |
14.57 |
10.54 |
5.98 |
4.24 |
|
1.67V |
65.84 |
44.80 |
34.40 |
28.21 |
24.15 |
17.80 |
14.08 |
10.27 |
5.86 |
4.15 |
|
1.70V |
62.23 |
42.90 |
33.30 |
27.47 |
23.60 |
17.42 |
13.84 |
10.14 |
5.80 |
4.11 |
|
1.75V |
56.25 |
39.80 |
31.60 |
26.20 |
22.67 |
16.80 |
13.47 |
9.90 |
5.69 |
4.04 |
|
1.80V |
50.26 |
36.40 |
29.70 |
24.87 |
21.66 |
16.23 |
13.12 |
9.66 |
5.59 |
3.98 |
|
1.85V |
43.25 |
32.87 |
27.63 |
23.45 |
20.65 |
15.59 |
12.71 |
9.38 |
5.50 |
3.91 |
|
Constant Power Discharge Characteristics
Unit:Watts (25℃,77℉) |
|
F.V/Time |
2MIN |
4MIN |
6MIN |
8MIN |
10MIN |
15MIN |
20MIN |
30MIN |
60MIN |
90MIN |
|
1.60V |
705.86 |
505.50 |
394.70 |
327.54 |
286.26 |
210.75 |
169.34 |
124.09 |
71.65 |
50.84 |
|
1.67V |
645.30 |
470.00 |
376.40 |
314.50 |
275.50 |
204.70 |
165.00 |
121.30 |
70.52 |
50.05 |
|
1.70V |
618.20 |
454.00 |
365.50 |
308.00 |
270.10 |
201.60 |
163.10 |
119.90 |
70.00 |
49.64 |
|
1.75V |
571.30 |
426.00 |
350.00 |
296.40 |
260.00 |
196.20 |
159.50 |
118.00 |
69.00 |
49.00 |
|
1.80V |
523.50 |
400.00 |
333.00 |
284.50 |
250.40 |
191.10 |
155.80 |
116.20 |
68.09 |
48.34 |
|
1.85V |
478.32 |
375.59 |
315.69 |
273.06 |
241.41 |
186.11 |
152.32 |
113.96 |
67.02 |
47.66 |
The HR1234WF2 should replace the following part numbers for most
applications, be sure to check dimensions, terminal size, voltage and amp hour
ratings.
| |
APC BACKUPS ES65 |
| |
APC BE650BB |
| |
APC BE650BBCN |
| |
APC BE650R |
| |
APC BE725BB |
| |
APC BN600 |
| |
APC BP700UC |
|
| |
APC RBC17 |
| |
CSB Battery HR1234W |
| |
CSB Battery HR1234WF2 |
| |
GS Battery PX12090 |
| |
Interstate Batteries
ASLA0020 |
| |
Minuteman E1500RM2U |
| |
Panasonic LCR129P |
|
| |
Panasonic LCR129P1 |
| |
Panasonic UPRW1245P1 |
| |
Powersonic PSH1280F2 |
| |
Powersonic PSH1280FR |
| |
Tempest TR8512 |
| |
Universal Power Group D2815 |
| |
UPRW1245P1 |
|
Typical applications for the
HR1234WF2 include:
Cycle Use
-
Portable VCR/TV,
tape recorders, radios and so on
-
Power tools, lawn
mowers, vacuum cleaners
-
Cameras and
photographic equipment
-
Portable personal
computers, word processors, portable
terminals, and so on
-
Portable measuring
equipment
-
Portable telephone
sets
-
Various power toys
and hobby equipment
-
Lighting equipment
Standby
Use
-
Communications and
electric equipment
-
Emergency lighting
equipment
-
Fire alarms and
security systems
-
Various telemeter
equipment
-
Office computers,
microcomputers, and other office
automation equipment
-
Robots, control
equipment, and other factory
automation equipment
-
UPS power supply
-
Emergency power
supply in power generation plants
and substations.
Solar Cell
Power Generation
-
Water pumping
systems
-
Portable power
supplies
-