Power Factor Inc. - 800-706-7009 www.powerfactorincdirect.com |
|
Find the battery you want at the right price @ batteries asap!
|
Dynasty C&D Battery UPS6-620 & UPS6-620FR have been replaced by the UPS6-620MRClick here to purchase the replacement UPS6-620MR Battery from our online store at batteriesasap.com UPS6-620
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
![]() |
![]() |
UPS6-620
Valve Regulated Lead Acid Battery
for UPS standby power applications
6V 200 AH @ 20 hr rate,
6V 620 watts/cell @ 15 min. rate
FEATURES

|
* All dimensions in
inches and (millimeters). All dimensions are for reference only. Contact
a C&D Representative for complete dimensional information.
|
|
UPS6-620 -
Specifications
|
||||||||
|
Cells
Per Unit |
Voltage
Per Unit |
Weight
|
Electrolyte
|
Maximum
Discharge Current |
Short Circuit
Current
|
Ohms Imped.
60 Hz |
||
|
3
|
6.42
|
72 lbs.
33 kg . |
Absorbed H2SO4
SG = 1.300 |
800 Amps
|
4350 Amps
@ 0.1 sec. |
0.0015 Ohms
|
||
|
Capacity |
620 watts per cell at the 15 minute rate to 1.67 volts per cell at 77°F (25°C). | |||||||
| 200 Ah @ 20 hr. rate to 1.75 volts per cell @ 77°F (25°C). | ||||||||
| 170 Ah @ 10 hr. rate to 1.80 volts per cell @ 20°C (68°F). | ||||||||
| Operating Temperature Range | Discharge; -40°F (-40°C) to +160°F (71°C) | Charge;
-10°F (-23°C) to +140°F (60°C). (with temperature compensation) |
||||||
|
Nominal Operating
Temperature Range |
+74°F (23°C) to +80°F (27°C). | |||||||
|
Float Charging Voltage
|
6.75 to 6.90 VDC/unit Average at 77°F (25°C). | |||||||
|
Recommended Maximum
Charging Current Limit |
C/5 amperes (40 amperes @ 100% depth of discharge) @ 20 hour rate. | |||||||
| Equalization and Cycle Service Charging Voltage | 7.2 to 7.4 VDC/unit Average at 77°F (25°C). | |||||||
| Maximum AC Ripple (Charger) | 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. | |||||||
| Maximum voltage allowed = 1.4% RMS (4% P-P). | ||||||||
| Maximum current allowed = 9 amperes RMS (C/20). | ||||||||
| Self Discharge | Dynasty UPS batteries may be stored for up to 6 months at 77°F (25°C) and then a freshening charge is required. For higher temperatures the time interval will be shorter. | |||||||
|
Accessories |
Inter unit connectors, racks and cabinet systems are available. | |||||||
|
Terminal |
"L" terminal with 0.28" clearance hole to accept 0.25" (6mm) bolt. | |||||||
|
Terminal Hardware Initial Torque |
75 in.-lbs. (8.5 N-m). | |||||||
| Terminal Hardware Annual Retorque | 60 in.-lbs. (6.8 N-m). | |||||||

|
Note:
|
Batteries to be mounted
with 0.5 in (1.25 cm) spacing minimum and free air ventilation.
Specifications subject to change without notification.
|
Buy batteries on-line and get it fast!
|
Power Factor Inc. / Batteries ASAP! 2526 Manana Suite 102 Dallas, Texas 75220 800-706-7009 Established 1996 While every precaution has been
taken to ensure accuracy and completeness in this literature, Power Factor Inc.
assumes no responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions. Specifications
subject to change without notice. |