Dynasty C&D Battery UPS12-475Dynasty C&D Battery Johnson Control UPS12-475 & UPS12-475FR have been replaced by the UPS12-490MRUPS12-475
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
![]() |
![]() |
UPS12-475
Valve Regulated Lead Acid
Battery
for UPS standby power applications
12V 134 AH @ 20 hr rate,
12V 475 watts/cell @ 15 min. rate
FEATURES


|
*All dimensions in
inches and (millimeters). All dimensions are for reference only. Contact a
C&D Representative for complete dimensional information.
|
|
UPS12-475 -
Specifications
|
||||||||
|
Cells Per Unit
|
Voltage Per Unit
|
Weight
|
Electrolyte
|
Maximum
Discharge Current |
Short Circuit
Current
|
Ohms Imped.
60 Hz |
||
|
6
|
12.84
|
100lbs.
45 kg. |
Absorbed H2SO4
SG = 1.300 |
800 Amps
|
5000 Amps
@ 0.1 sec. |
0.0023 Ohms
|
||
|
Capacity |
475 watts per cell at the 15 minute rate to 1.67 volts per cell at 77°F (25°C). | |||||||
| 134 Ah @ 20 hr. rate to 1.75 volts per cell @ 77°F (25°C). | ||||||||
| 122 Ah @ 10 hr. rate to 1.80 volts per cell @ 20°C (68°F). | ||||||||
| Operating Temperature Range | Discharge; -40°F (-40°C) to +160°F (71°C). | Charge; -10°F (-23°C) to +140°F (60°C). (with temperature compensation) | ||||||
| Nominal Operating Temperature Range | +74°F (23°C) to +80°F (27°C). | |||||||
|
Float Charging Voltage
|
13.5 to 13.8 VDC/unit Average at 77°F (25°C). | |||||||
| Recommended Maximum Charging Current Limit | C/5 amperes (27 amperes @ 100% depth of discharge). | |||||||
| Equalization and Cycle Service Charging Voltage | 14.4 to 14.8 VDC/unit Average at 77°F (25°C). | |||||||
| Maximum AC Ripple (Charger) | 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. | |||||||
| Maximum voltage allowed = 1.4% RMS (4%P-P). | ||||||||
| Maximum current allowed = 6.7 amperes (C/20). | ||||||||
| Self Discharge | Dynasty UPS batteries may be stored for up to 6 months at 77°F (25°C) and then a freshening charge is required. For higher temperatures the time interval will be shorter. | |||||||
|
Accessories |
Inter unit connectors, racks and cabinet systems are available. | |||||||
|
Terminal |
Threaded brass inserts to accept 0.25" (6mm) bolt. | |||||||
|
Terminal Hardware Torque |
110 in.-lbs. (12.4 N-m) | |||||||


|
Note:
|
Batteries to be mounted
with 0.5 in. spacing minimum and free air ventilation. Specifications
subject to change without notification.
|
Buy batteries on-line and get it fast!
|
Power Factor Inc. / Batteries ASAP! 2526 Manana Suite 102 Dallas, Texas 75220 800-706-7009 Established 1996 While every precaution has been
taken to ensure accuracy and completeness in this literature, Power Factor Inc.
assumes no responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions. Specifications
subject to change without notice. |